Description
The Bitmain ANTRACK AR30 is a professional 200 kW Hydro mining and heat-recovery system built around a standard 47U rack. It supports up to 20 Antminer U2 Hydro miners or 14 traditional Hydro miners and integrates an industrial plate heat exchanger to transfer mining heat into compatible hydronic heating systems. Designed for mining farms, commercial buildings, greenhouses, pools and other facilities where recovered heat can be reused, the AR30 combines high-density mining infrastructure with practical thermal-energy recovery. Next Level Corp provides local sales, deployment guidance and long-term technical support.
| Manufacturer | Bitmain |
|---|---|
| Model | ANTRACK AR30 |
| Product type | 47U Hydro mining and heat-recovery cabinet |
| Form factor | 47U industrial rack system |
| Installed capacity | Up to 20 × Antminer U2 Hydro miners or 14 × traditional Antminer Hydro miners |
| Miner maximum load | 200 kW |
| Total system load | 207 kW |
| Cooling / Heat recovery | Closed-loop Hydro cooling with integrated industrial plate heat exchanger (PHE) |
| Electrical input | 380–480 V AC · 3-phase · 50–60 Hz |
| Maximum input current | 315 A @ 380 V · 249 A @ 480 V |
| Water pipe connector | DN50 |
| Coolant inlet temperature | -20 to 45 °C |
| Water flow | 320–350 L/min |
| Maximum water pressure | ≤3.5 bar |
| Working fluid | Organic antifreeze solution, approximately 10% |
| Liquid pH | 7.8–8.5 |
| Maximum installation distance | ≤5 m |
| Storage temperature | -40 to 70 °C |
| Operating humidity | 10–90% RH, non-condensing |
| Compatible miner formats | 2U server-form Hydro miners and traditional vertical Hydro miners |
| Compatible models (examples) | Antminer L9 Hyd 2U, L11 Hyd 2U, S23e Hyd 2U, S19 Hydro series, S21 Hydro series, S23 Hydro series and other compatible Antminer Hydro models |
| Cabinet dimensions | 1000 × 1200 × 2300 mm |
| Packaged dimensions | 1070 × 1380 × 2400 mm |
| Weight | Approximately 780 kg |
Notes
- The ANTRACK AR30 requires a professional 380–480 V three-phase electrical installation sized for continuous industrial mining loads.
- The integrated plate heat exchanger keeps the miner coolant loop isolated from the secondary building or process-heating circuit.
- Recovered thermal energy can be integrated into compatible hydronic applications such as building heating, radiant floors, greenhouses, pools or process-heating systems.
- The facility receiving the recovered heat must provide sufficient thermal demand and compatible hydronic infrastructure.
- Miner capacity depends on the physical format and electrical consumption of the installed Hydro miners.
- Verify transformer capacity, electrical distribution, protection devices, grounding, plumbing, heat-recovery loop design and installation space before deployment.
- Two freight options are available: Air Freight with an estimated 15-day delivery time and Sea Freight with an estimated 45-day delivery time.
Your purchase includes (Next Level Corp)
- Pre-installation compatibility and deployment guidance.
- Guidance for electrical, Hydro and heat-recovery installation requirements.
- Configuration assistance for compatible Hydro mining equipment.
- Guidance for integration with compatible hydronic heating infrastructure.
- Remote technical assistance during setup and commissioning.
- Pool and wallet configuration assistance for installed miners.
- Lifetime 24/7 technical advice.
- Genuine spare parts and compatible Hydro accessories available for sale.
- Local service and technical support in Bolivia.
- Manufacturer warranty according to the applicable equipment and purchase terms.
This product is available with two freight options: Air Freight or Sea Freight. Select the preferred shipping option above to display the corresponding price and estimated delivery time.
Important Notice:
The ANTRACK AR30 is industrial mining and heat-recovery infrastructure and requires appropriate three-phase electrical capacity, Hydro plumbing, installation space and professional commissioning. The 200 kW specification refers to the maximum supported miner load and is not the power consumption or hashrate of an individual ASIC miner. Heat-recovery performance depends on the installed mining load, coolant conditions and the thermal demand of the connected facility.
Tags: ANTRACK, ANTRACK AR30, Bitmain ANTRACK, Hydro, Hydro Mining, Minería Hydro, Heat Recovery, Recuperación de calor, Mining Heat Recovery, Rack de minería, Gabinete de minería, Mining Rack, Mining Cabinet, 200 kW, 47U, Plate Heat Exchanger, PHE, Intercambiador de calor, Refrigeración líquida, Sistema de refrigeración líquida para minería, Data Center, Centro de datos, Antminer Hydro, Antminer 2U Hydro.










Reviews
There are no reviews yet.